Function:
It is a kind of organic corrosive and scale inhibitor composed of organic phosphonic acid, carboxylic-acid polymer and copper corrosive inhibitor. It can be used in wide PH range with excellent scale inhibition effect.
Uses:
When used in recirculated cooling water in power plant, it shows good anticorrosive effect on heat exchanger made by copper, aluminum and carbon steel. The usual use level is 10-20mg/L. It can be used in recirculated cooling water in petrochemical factory, fertilizer factory, steel plant and refinery, the usual use level is 20-50mg/L.
Specification:
Appearance: colorless or yellowish transparent liquid
Density(20 ): 1.0-1.3g/cm3
pH (1% aqueous solution):1.0-3.0
Solid Content: 30%
Usage:
20-50mg/L under normal operation, adding them once or three times every day.
Package and Storage:
plastic drum(net weight: 25kg/drum), stored in ventilated, shady and cool place;
Period of validity: one year.
|